SERVICES AND LABS

HIGH VOLTAGE TESTING


HIGH VOLTAGE TESTING HALL

The screened High Voltage testing hall,
40 m × 25 m × 25 m (h),
is the main room of the HV Laboratory. It is equipped with a
power frequency generator up to 1 MV
(50 Hz / 60 Hz), and an impulse voltage generator up to
2.8 MV for lightning impulses and
1.8 MV for switching impulses.


MEDIUM VOLTAGE TESTING HALL

The screened Medium Voltage hall,
29 m × 13 m × 12 m (h),
is the secondary test hall. It is divided into
five testing cells to perform power frequency tests
up to 150 kV, lightning impulse tests up to
400 kV, temperature-rise tests, ratio and phase
measurements on current transformers, high-sensitivity partial
discharge measurements (Faraday Cage), and other performance tests
on distribution and medium-power transformers and prefabricated
substations.


INDIVIDUAL TESTING AREAS ALLOW SIMULTANEOUS TESTING OF DIFFERENT ITEMS
 MAXIMUM VOLTAGE OR CURRENTSTANDARDS
IMPULSE TESTING
Lightning Impulse2000 kV 1.2/50 usIEC, ANSI, CENELEC
Switching Impulse (Dry & Wet)1600 kV 250/2500 usIEC, ANSI, CENELEC
AC TESTING
Dry tests850 kV, 50-60 HzIEC, ANSI, CENELEC
Wet tests800 kV, 50-60 HzIEC, ANSI, CENELEC
Induced tests700 kV 100-200 HzIEC, ANSI, CENELEC
AC Current8000 A 50-60 HzIEC, ANSI, CENELEC
DC TESTING
Dry & Wet800 kV 20 mAIEC, ANSI, CENELEC
DC Current5000 A, DCIEC, ANSI, CENELEC
OTHER TEST
Partial Discharge Measurement700 kVIEC, ANSI
RIV Measurement400 kVCISPR18, NEMA
Capacitance & Tan & measurement200 kV, 50-60 HzIEC, ANSI
Pollution Testing240 kV 
Temperature-rise tests8000 A 50-60 Hz 


CLIMATIC CHAMBER


DIMENSIONS: 5 m LENGTH × 2 m WIDTH × 3 m HEIGHT

CLIMATIC TESTINGSTANDARDRANGE OF TEMPERATURE
Icing, Environmental TestsIEC-40 °C up to +60 °C, up to 95 % HR

HIGH POWER TESTING

By means of an agreement with HPL (laboratory of Ormazabal group, located in Boroa, Bilbao), combining personnel, expertise and measurement systems of LCOE with the HPL facilities.

TESTRATINGS
MEDIUM VOLTAGE TESTS (up to 36 kV AC)
Short time and peak withstand current40 kA / 3 s (50-60 Hz)
Short-circuit making and breaking tests16 kA/40.5 kV; 20 kA/36 kV; 31.5 kA/24 kV; 40 kA/12 kV (50-60 Hz)
Making and breaking of active loadsup to 2000 A /40,5 kV (50-60 Hz)
Making and breaking of capacitive loadsup to 100 A /40,5 kV (50-60 Hz)
Internal arc tests40 kA for 1 s (50-60 Hz)
Transformers short circuitup to 20 MVA /36 kV (50-60 Hz)
LOW VOLTAGE TESTS (up to 700 V AC)
Short time and peak withstand currentlth 100 kA for 1 s/ ldyn 250 kA (50-60 Hz)
Internal arc tests80 kA for 1 s (50-60 Hz)


COMPONENTS TESTED

  • Instrument transformers
  • Switchgear (MV and LV)
  • Power transformers
  • Cables and accessories
  • R&D+i applications


TESTS AVAILABLE

  • Short time and peak withstand current tests
  • Short circuit tests
  • Switching tests
  • Power arc tests
ⓘ More information: jose.bregel@ffii.es

HIGH CURRENT IMPULSES TESTS

The high current impulse tests are performed in a separate, specific chamber from the general high voltage tests. This chamber was designed by LCOE as an internal R&D project in order to meet the demand on Aircraft Lightning Direct Effect tests. Since the beginning, the high current laboratory has continued evolving by diversifying its test catalogue. These test catalogue ratings are summarized in the table below.

ⓘ More information: angel.ramirez@ffii.es
WAVEFORMSRATINGS
AIRCRAFTS
High Current TestingAll waveforms and zones defined by the standard
High Voltage Testing     Waveforms A and B up to 2000 kV
Waveform D up to 1600 kV
HIGH VOLTAGE SURGE ARRESTERS
DistributionUp to Heavy Duty Distribution Qrs ≥ 0.4 pC
SubstationUp to Substation Low. Qrs ≥ 1&nbspC. Wth≥ 4 kJ/kV
LIGHTNING PROTECTION SYSTEM COMPONENTS
Waveform 10/350 µsUp to 200 kA